Earth Fault-Loop Impedance Part 3

Category: Tutorials

In Part 2, we did a simple calculation for the maximum length of the cable. We have not considered the internal impedance of the source, i.e. the transformer impedance. Likewise, we just consider the current rating of the circuit breaker without the current multiplier for instantaneous tripping. The primary reason for that is to make the calculation much simpler. If I will tell everything all at once, understanding the concept may be difficult.

Read more ...

Earth Fault-Loop Impedance Part 2

Category: Tutorials

As mentioned in Part 1, the value of the fault loop impedance shall be able to generate enough fault current to activate any protective device.

What does this mean? The earth fault current must be high enough to trigger the automatic disconnection of a protective device within an specified time. If the value of the earth fault current is not within the tripping current of the protective device, then there will be no means of protective device will provide protection against touch voltage. At the location of the fault, there is a possibility that the full voltage is present in the equipment enclosure posing hazard to people with the increased touch voltage higher than 50 Vac.

Read more ...

Earth Fault-Loop Impedance Part 1

Category: Tutorials

What is "Earth Fault-Loop Impedance"? Why is it important?

Standards define "Earth Fault-Loop Impedance" as the impedance of the earth fault-current loop (active-to-earth loop) starting and ending at the point-of-earth fault.

It is important to know the earth fault-loop impedance of a circuit to ensure that during the occurence of a phase-to-earth fault, normally an insulation fault, the magnitude of the fault current is enough to cause the operation of the protective device within the required time particularly where the touch potential exceeds 50V a.c. or 120V ripple-free d.c.

Read more ...

Time-Current Curves with Excel IV

Category: Tutorials

This is the final part of the tutorial creating for time-current current curves with Excel. We shall be able to attain a complete relay coordination similar to this following curve.

Complete Time Current Curve

Read more ...

Time-Current Curves with Excel III

Category: Tutorials

In this tutorial, we shall be able to create Normal Inverse curves from the formula given below (IEC). This formula has been used in so many coordination studies world wide. You can actually use it to coordinate your protection settings with your power supplier. Normally the time setting for the network protection will be provided by the power supplier. We shall be discussing this on the next tutorial.

Curve Formula
Time-Current Formula
where

k = time, s
α, β = constants, see table below
I = Input Current
IO = Pickup setting

Read more ...

  1. Time-Current Curves with Excel II
  2. Creating Coordination Curves with Excel
  3. Hign Voltage Switchgear Rated Insulation Level
  4. Power Factor Correction - Tutorial (Part 2)